Second law assessment of di methyl ether and its mixtures in domestic refrigeration system
HomeHome > News > Second law assessment of di methyl ether and its mixtures in domestic refrigeration system

Second law assessment of di methyl ether and its mixtures in domestic refrigeration system

Jun 21, 2023

Scientific Reports volume 13, Article number: 275 (2023) Cite this article

759 Accesses

Metrics details

Dimethyl ether (DME) and its blend of refrigerants (R429A, R435A, and R510A) are considered in this study's second law analysis as potential replacements for R134a. The performance of various refrigerants in a vapour compression refrigeration system is examined using the Design package CYCLE D. The software REFPROP 9.0 is used to extract all of the thermal and physical parameters of DME and its blend of refrigerants. The Second law performance parameters such as Efficiency Defects, Entropy generation and ExergyEfficiency are discussed. The refrigerants R429A and R510A are more energy efficient than R134a across a condensing temperature range of 30 to 55 °C at − 10 °C evaporation temperature. R134a was exceeded by R429A and R510A in terms of exergetic efficiency by 2.08 and 0.43%, respectively. In comparison to other losses in different components, the compressor's exergy loss is larger at 37–40% of the total exergy loss. By employing RE170 and its blends, the Vapour Compression Refrigeration System often performs better under the second law than R134a.

The result shows that the efficiency defects in the compressor are the largest, followed by the condenser and evaporator. Thus, the design improvement of a compressor is of at most importance to improve the system performance by lowering the overall irreversibility.

R134a is effectively used in domestic refrigerators (GWP 1430) as an alternative to CFC, which has high ODP and GWP1,2. The Kyoto Protocol from 1997 designated it as a greenhouse gas; thus, its production and use will end within the next decades. As a result, ecologically friendly refrigerants will take their place3,4. According to EU regulations, it is now essential to find a replacement refrigerant with a low GWP5,6. Table 1 lists the physical characteristics of the refrigerants under investigation. According to Nicholas Cox7, the absence of temperature glide and separation makes the Di methyl ether perform better than the hydrocarbon blend. Valentinapostol et al.8 make a comparative thermodynamic analysis using refrigerants R717, R12, R134A, R22, DME, and mix R404A, R407C in a refrigeration system. DME could be utilized as a refrigerant and a good replacement for R12 and R134a, according to the findings of this study.

The Di methyl ether (DME, C2H6O), according to B.M. Adamson9, possesses a number of desirable characteristics as a replacement for R134a. A few of these are enhanced heat transfer capabilities, favourable pressure/temperature stability with natural lubricants, relatively inexpensive, and prompt access. It's also very eco-friendly, and it's compatible with the majority of materials used in refrigeration systems.

Various researchers10,11,12,13,14,15,16,17,18,19,20,21,22,23,24,25,26,27,28,29,30,31 analyzed the thermal performance of VCR systems with DME and its blends. The result indicates that the investigated refrigerants are conformed as possible alternatives to R134a. Ki-Jung Park et al.32 investigated the domestic water purifier performance using R429A. The results indicate that the discharge temperature of the compressor and energy consumption is 13.40 C and 28.9% lower when compared with R134a. Choedaeseong et al.33 investigated the performance of R435A (a combination of DME and R152a) as a replacement for R134a in-home water purifiers. In comparison to HFC 134a, the electricity usage and release temperatures were respectively 12.7% and 3.7 °C lower. Through the use of R510A, Ki-Jung Park et al.34 examined the performance of household water purifiers. The result indicates that the discharge temperature of the compressor and energy consumption is 3.70 C and 22.3% lower when compared with R134a35,36. In this study, the second law performance of the system is investigated with the refrigerants RE170, R429A, R435Aand R510A as possible alternatives to R134a.

Figures 1 and 2 show the refrigeration system's block diagram and P–H diagram.

Block diagram of a refrigeration system.

P–H diagram refrigeration system.

The details of the operating cycle are as follows.

Isentropic compression (Stage 1–2).

Condensation (Stage 2–3).

Throttling (Stage 3–4).

Evaporation (Stage 4–1).

The equations used for exergy analysis in different components:

Exergy:

Evaporator:

Abstraction of heat

Exergy losses,

Compressor:

Exergy loss,

Condenser:

Exergy loss,

Expansion Valve:

Exergy loss,

Total exergy loss,

Efficiency defect:

For Compressor,

Condenser,

Expansion valve,

Evaporator,

Exergy Efficiency,

For the application of R134a, Di methyl ether, and the following chosen mixtures, a theoretical study was carried out.

R510A is made up of 88% and 12%, a blend of RE170 and R600a.

R435A is made up of an 80% and 20% blend of RE170 and R152a

R 429A is made up of a 60%, 30%, and 10% mixture of RE170, R600a, and R152a.

The following conditions were taken into consideration when the behaviour of the vapour compression refrigeration system was examined using the CYCLE D 4.0 programme36.

The isentropic and volumetric efficiency of the compressor = 0.75.

Cooling capacity = 1.00 kW.

The efficiency of the Electric motor = 0.75.

Suction line heat exchanger efficiency = 0.80.

Operating temperature of Evaporator =  − 50 °C to + 20 °C.

Operating temperature of Condenser = 45 °C.

Superheating temperature = 10 °C.

Subcooling temperature = 5 °C.

To obtain the enthalpy and entropy values required for the study, REFPROP 9.0 is employed35. This theoretical study examines the impact of energetic efficiency (Ex.eff) and efficiency flaws (Exd) in system components. The variation of Exergy Efficiency against the evaporating and condensing temperature is shown in Figs. 3 and 4, respectively. The variation of Efficiency defects (Exd) in system components are plotted in the figures from 5 to 6. The observations and Deviations of second law performance parameters in the VCR System are presented in Tables 2 and Table 3. Entropy generation in Various Components are presented in Table 4. Exergy losses in Various Components are listed in Table 5.

Exergy Efficiency as a Function of Evaporating Temperature.

Exergy Efficiency and Condensing Temperature.

Figure 3 indicates the effect of Exergetic efficiency (ηex) in changing temperatures for evaporation. When the temperature of the evaporator rises, the exergy efficiency furthermore increases up to the optimum evaporator temperature, and after that, it will decrease. The most Exergetic efficiency is achieved at optimum evaporator temperature. The difference in exergy efficiency is caused by two things. One is the exergy. The second issue is the work that must be done on the compressor. As the temperature of the evaporator rises, the compressor's work decreases. As a result, these two elements improve exergy efficiency until it reaches the optimum evaporator temperature, beyond which it drops. At lower evaporation temperatures, the refrigerant R429A has a greater energy efficiency than R134a. At increasing evaporation temperatures, the exergetic efficiency of all chosen refrigerants has improved. Over a wide range of evaporation temperatures, R429A has a higher Exergetic efficiency value than R134a. R429A has a 1.6–2.3% better exergetic efficiency than R134a.

The influence of condensation temperatures on exergetic efficiency (ex) is seen in Fig. 4. Exergetic efficiency decreases as condenser temperatures rise. At lower condensation temperatures, the refrigerant R429A has more energy efficiency than R134a. At higher condensation temperatures, the exergetic efficiency of all chosen refrigerants has improved. Over a wide range of condensing temperatures, R429A and R510A have higher exergetic efficiency than R134a. R429A has a 0.30–2.49% higher exergetic efficiency than R134a.

With various evaporator temperatures, Fig. 5 depicts the effect of an efficiency flaw in the compressor for R510A, RE170, R429A, R435A, and R134a. The compressor efficiency defect grows as the temperature in the evaporator rises, as shown in the graph. The results show that R510A, R435A, R429A, and RE170 have less compressor efficiency defects than R134a.

Compressor efficiency defect as a function of evaporator temperature.

Figure 6 indicates the effect of efficiency defect in the condenser for R510A, RE170, R429A, R435A and R134a with varying evaporator temperature. The figure reveals that the condenser efficiency defect reduces with rise in evaporator temperature up to − 25 °C and then increases. The result indicates that the condenser efficiency defects for investigated refrigerants are more than that of R134a.

Condensor efficiency defect as a function of evaporator temperature.

For RE170, R429A, R435A, R510A, and R134a, Fig. 7 depicts the effect of an expansion valve efficiency failure as evaporator temperature varies. The expansion valve efficiency defect reduces with increasing evaporator temperature up to − 10 °C and thereafter increases, as seen in the graph. RE170, R429A, R435A, and R510A have lower expansion valve efficiency defects than R134a, according to the results37,38,39.

Expansion valve efficiency defect as a function of evaporator temperature.

For RE170, R429A, R435A, R510A, and R134a, Fig. 8 depicts the effect of an evaporator efficiency fault as a function of evaporator temperature. The evaporator efficiency defect increases when the temperature in the evaporator rises to − 15 °C and then declines, as seen in the graph. The evaporator efficiency fault for R510A, R435A, R429A, and RE170 is higher than R134a, according to the results40,41.

Evaporator efficiency defect as a function of evaporator temperature.

The effect of a suction line heat exchanger efficiency fault on evaporator temperature for RE170, R429A, R435A, R510A, and R134a is shown in Fig. 9. When the temperature in the evaporator rises, the efficiency defect in the suction line heat exchanger reduces, as shown in the graph. The results show that RE170, R429A, R435A, and R510A have lower suction line heat exchanger efficiency defects than R134a.The heat exchanger (suction line–capillary tube) achieved a good enhancement in COP and effectiveness compared with the reference capillary tube (without suction line) due to the increase in the sub-cooling zone42,43,44.

Heat exchanger efficiency defect as a function of evaporator temperature.

The performance of the VCR system under the second law is investigated for the refrigerants R510A, R435A, R429A, and RE170. On the performance parameter, the impacts of evaporating temperature and condensing temperature are shown.

The observations in this analysis are given as follows.

The refrigerants R429A and R510A are more energy efficient than R134a across a condensing temperature range of 30 to 55 °C at − 10 °C evaporation temperature.R429A and R510A had better exergetic efficiency than R134a by 0.31–2.46% and 0.37–1.29%, respectively.

In compressor, the loss of exergy is 37–40% of the total exergy loss, which is higher than the other losses in various components.

Mostly efficiency defect with R429A and R510A in the system is systematically better than R134a.

The highest efficiency defects were obtained using selected refrigerants in Compressor, condenser and evaporator.

By employing RE170 and its blends, the Vapour Compression Refrigeration System generally performs better under the second law than R134a.

The datasets used and analysed during the current study available from the corresponding author on reasonable request.

Di methyl ether

Global warming potential

Ozone layer depletion

Normal boiling point

Hydro fluro carbon

Vapour compression refrigeration

Exergy (kW)

Enthalpy (kJ/kg)

Temperature (°C)

Entropy (kJ/kg.K)

Mass flow rate (kg/sec)

Irreversibility in evaporator (kW)

Refrigeration effect (kW)

Evaporator temperature (°C)

Electrical power (kW)

Heat dissipated in condensor (kW)

Irreversibility in condensor (kW)

Condensor temperature (°C)

Total irreversibility (°C)

Irreversibility in expansion valve (kW)

Irreversibility in compressor (kW)

Efficiency defect in expansion valve

Efficiency defect in compressor

Efficiency defect in condensor

Efficiency defect in evaporator

Exergy efficiency

Entropy generation (kW/K)

Baskaran, A., Manikandan, N., Tesfaye, J. L., Nagaprasad, N. & Krishnaraj, R. Exergy performance investigation of eco-friendly refrigerant mixtures as an alternative to R134a in a domestic refrigerator. Int. J. Photoenergy 2022, 1–9 (2022).

Article Google Scholar

Eyal, A. & Tartakovsky, L. Second-law analysis of the reforming-controlled compression ignition. Appl. Energy 263, 114622 (2020).

Article CAS Google Scholar

Tsai, W.-T. An overview of environmental hazards and exposure risk of hydrofluorocarbons (HFCs). Chemosphere 61, 1539–1547 (2005).

Article ADS CAS Google Scholar

Ogle, S. M. et al. Delineating managed land for reporting national greenhouse gas emissions and removals to the United Nations framework convention on climate change. Carbon Balance Manag. 13, 1–13 (2018).

Article Google Scholar

Wawrzyczek, J., Lindsay, R., Metzger, M. J. & Quétier, F. The ecosystem approach in ecological impact assessment: Lessons learned from windfarm developments on peatlands in Scotland. Environ. Impact Assess. Rev. 72, 157–165 (2018).

Article Google Scholar

Harby, K. Hydrocarbons and their mixtures as alternatives to environmental unfriendly halogenated refrigerants: An updated overview. Renew. Sustain. Energy Rev. 73, 1247–1264 (2017).

Article CAS Google Scholar

Yelishala, S. C. et al. Thermodynamic study on blends of hydrocarbons and carbon dioxide as zeotropic refrigerants. J. Energy Resour. Technol. 142, 82304 (2020).

Article CAS Google Scholar

Emani, M. S. & Mandal, B. K. The use of natural refrigerants in refrigeration and air conditioning systems: A review. IOP Conf. Ser. Mater. Sci. Eng. 377, 12064 (2018).

Article Google Scholar

Dalkilic, A. S. & Wongwises, S. A performance comparison of vapour-compression refrigeration system using various alternative refrigerants. Int. Commun. Heat Mass Transf. 37, 1340–1349 (2010).

Article CAS Google Scholar

Zhang, L., Zhao, J., Yue, L., Zhou, H. & Ren, C. Cycle performance evaluation of various R134a/hydrocarbon blend refrigerants applied in vapor-compression heat pumps. Adv. Mech. Eng. 11, 1687814018819561 (2019).

CAS Google Scholar

Thavamani, J. & Senthil, R. Performance analysis of retrofitted domestic vapour compression refrigeration system using hydrocarbon refrigerants. Int. J. Ambient Energy 43, 2549–2556 (2022).

Article CAS Google Scholar

Mani, K. & Selladurai, V. Experimental analysis of a new refrigerant mixture as drop-in replacement for CFC12 and HFC134a. Int. J. Therm. Sci. 47, 1490–1495 (2008).

Article CAS Google Scholar

Sarkar, J. & Bhattacharyya, S. Assessment of blends of CO2 with butane and isobutane as working fluids for heat pump applications. Int. J. Therm. Sci. 48, 1460–1465 (2009).

Article CAS Google Scholar

Kujak, S. & Schultz, K. Insights into the next generation HVAC&R refrigerant future. Sci. Technol. Built Environ. 22, 1226–1237 (2016).

Article Google Scholar

Bayrakçi, H. C. & Özgür, A. E. Energy and exergy analysis of vapor compression refrigeration system using pure hydrocarbon refrigerants. Int. J. Energy Res. 33, 1070–1075 (2009).

Article Google Scholar

Agrawal, S. K., Kumar, R. & Khaliq, A. First and second law investigations of a new solar-assisted thermodynamic cycle for triple effect refrigeration. Int. J. Energy Res. 38, 162–173 (2014).

Article Google Scholar

Deng, R., Jing, X., Zheng, D. & Li, X. Vapor–liquid equilibrium measurements and assessments of fluoroethane+ N, N-dimethylformamide and fluoroethane+ dimethyletherdiethylene glycol systems for the hybrid refrigeration cycle. Int. J. Refrig. 43, 176–186 (2014).

Article CAS Google Scholar

Gil, B., Fievez, A. & Zajaczkowski, B. Pool boiling heat transfer coefficient of dimethyl ether and its azeotropic ternary mixtures. Int. J. Heat Mass Transf. 171, 121063 (2021).

Article CAS Google Scholar

Zhang, X. & Hu, D. Performance analysis of the single-stage absorption heat transformer using a new working pair composed of ionic liquid and water. Appl. Therm. Eng. 37, 129–135 (2012).

Article CAS Google Scholar

Thamilarasan, J., Kolappan, S. & Shanjeevi, C. Exergy comparison of vapour adsorption refrigeration systems. Int. J. Ambient Energy 41, 553–555 (2020).

Article CAS Google Scholar

Krishnamoorthi, M. & Malayalamurthi, R. Availability analysis, performance, combustion and emission behavior of bael oil-diesel-diethyl ether blends in a variable compression ratio diesel engine. Renew. Energy 119, 235–252 (2018).

Article CAS Google Scholar

Krishnamoorthi, M. & Malayalamurthi, R. Experimental investigation on performance, emission behavior and exergy analysis of a variable compression ratio engine fueled with diesel-aeglemarmelos oil-diethyl ether blends. Energy 128, 312–328 (2017).

Article CAS Google Scholar

Zapata-Mina, J. et al. Exergy analysis in a HCCI engine operated with diethyl ether-fusel oil blends. Case Stud. Therm. Eng. 32, 101899 (2022).

Article Google Scholar

Zhang, X., Cai, L., Chen, T., Qiao, J. & Zhang, X. Vapor-liquid equilibrium measurements and assessments of Low-GWP absorption working pairs (R32+ DMETEG, R152a+ DMETEG, and R161+ DMETEG) for absorption refrigeration systems. Energy 224, 120082 (2021).

Article CAS Google Scholar

Baskaran, A., Manikandan, N., Tesfaye, J., Nagaprasad, N. & Krishnaraj, R. Investigation on the performance of domestic refrigerator with zirconium oxide-R134a nanorefrigerant. J. Nanomater. 2022, 1–11 (2022).

Article Google Scholar

Hasheer, S. M., Srinivas, K. & Bala, P. K. Energy analysis of HFC-152a, HFO-1234yf and HFC/HFO mixtures as a direct substitute to HFC-134a in a domestic refrigerator. Stroj. Čas. J. Mech. Eng. 71, 107–120 (2021).

Google Scholar

Aprea, C., Greco, A. & Maiorino, A. HFOs and their binary mixtures with HFC134a working as drop-in refrigerant in a household refrigerator: Energy analysis and environmental impact assessment. Appl. Therm. Eng. 141, 226–233 (2018).

Article CAS Google Scholar

Wang, H., Zhao, L., Cao, R. & Zeng, W. Refrigerant alternative and optimization under the constraint of the greenhouse gas emissions reduction target. J. Clean. Prod 296, 126580 (2021).

Article CAS Google Scholar

Missaoui, S., Driss, Z., Slama, R., Ben, B. & Chaouachi, B. Experimental and numerical analysis of a helical coil heat exchanger for domestic refrigerator and water heating. Int. J. Refrig. 133, 276–288 (2022).

Article Google Scholar

Sánchez, D., Andreu-Nácher, A., Calleja-Anta, D., Llopis, R. & Cabello, R. Energy impact evaluation of different low-GWP alternatives to replace R134a in a beverage cooler. Experimental analysis and optimization for the pure refrigerants R152a, R1234yf, R290, R1270, R600a and R744. Energy Convers. Manag. 256, 115388 (2022).

Article Google Scholar

Borikar, S. A. et al. A case study on experimental and statistical analysis of energy consumption of domestic refrigerator. Case Stud. Therm. Eng. 28, 101636 (2021).

Article Google Scholar

Soylemez, E., Alpman, E. & Onat, A. Experimental analysis of hybrid household refrigerators including thermoelectric and vapour compression cooling systems. Int. J. Refrig 95, 93–107 (2018).

Article Google Scholar

Maiorino, A. et al. R-152a as an alternative refrigerant to R-134a in domestic refrigerators: An experimental analysis. Int. J. Refrig. 96, 106–116 (2018).

Article CAS Google Scholar

Aprea, C., Greco, A., Maiorino, A. & Masselli, C. The drop-in of HFC134a with HFO1234ze in a household refrigerator. Int. J. Therm. Sci. 127, 117–125 (2018).

Article CAS Google Scholar

Papadopoulos, A. I. et al. Systematic assessment of working fluid mixtures for absorption refrigeration based on techno-economic, environmental, health and safety performance. Energy Convers. Manag. 223, 113262 (2020).

Article CAS Google Scholar

Sekhar, S. J., Lal, D. M. & Renganarayanan, S. Improved energy efficiency for CFC domestic refrigerators retrofitted with ozone-friendly HFC134a/HC refrigerant mixture. Int. J. Therm. Sci. 43, 307–314 (2004).

Article CAS Google Scholar

Park, K.-J., Lee, Y.-H., Jung, D.-S. & Kim, K.-K. Performance of R430A on refrigeration system of domestic water purifiers. Korean J. Air Cond. Refrig. Eng. 21, 109–117 (2009).

Google Scholar

Baskaran, A. & Koshy Mathews, P. Energy and exergy analysis of a vapour compression refrigeration system with R134a, R152a and RE170. Arch. Des Sci. 66(3), 1–15 (2013).

Google Scholar

Akhilesh, A., Arora, B. B., Pathak, B. D. & Sachdev, H. L. Exergy analysis of a vapour compression refrigeration system with R-22, R-407C and R-410A. Int. J. Exergy 4(4), 441 (2007).

Article Google Scholar

Baskaran, A., Manikandan, N., & Sureshkumar, V. P. (2018) Thermodynamic analysis of di methyl ether and its blends as alternative refrigerants to R134a in a vapour compression refrigeration system. Development 5(12), ISSN NO: 2279-543X.

Baskaran, A., Manikandan, N. & Sureshkumar, V. P. Thermodynamic and thermophysical assessment of dimethyl ether and its blends application in household refrigerator. Int. J. Sci. Res. Rev. 7(2), 3668458 (2018).

Google Scholar

Salem, T., Farhan, S. & Farhan, I. Energy and exergy analysis study of heat exchanger in a refrigeration system with different lengths of capillary tube. Int. J. Thermodyn. 23(4), 260–266 (2020).

Article CAS Google Scholar

Ammar, A. F. (2016) Experimental and Numerical Study for Refrigerant Flow through Capillary Tube within Metastable Region. A Thesis for Master of Science in Mechanical Engineering, University of Babylon, Babylon.

Fatouh, M. & Abou-Ziyan, H. J. Energy and exergy analysis of a household refrigerator using a ternary hydrocarbon mixture in tropical environment—Effects of refrigerant charge and capillary length. Appl. Thermal Eng. 145, 14–26 (2018).

Article CAS Google Scholar

Download references

Department of Mechanical Engineering, P.A. College of Engineering and Technology, Pollachi, 642002, Tamilnadu, India

A. Baskaran & N. Manikandan

Department of Mechanical Engineering, ULTRA College of Engineering and Technology, Madurai, 625104, Tamilnadu, India

N. Nagaprasad

Centre for Excellence-Indigenous Knowledge, Innovative Technology Transfer and Entrepreneurship, Dambi Dollo University, Dambi Dollo, Ethiopia

Krishnaraj Ramaswamy

Department of Mechanical Engineering, Dambi Dollo University, Dambi Dollo, Ethiopia

Krishnaraj Ramaswamy

You can also search for this author in PubMed Google Scholar

You can also search for this author in PubMed Google Scholar

You can also search for this author in PubMed Google Scholar

You can also search for this author in PubMed Google Scholar

Conceptualization, B.A., M.N., N.N. and K.R.; Data curation, B.A., M.N., N.N. and K.R.; Formal analysis, B.A., M.N., N.N. and K.R.; Investigation, B.A., M.N., N.N. and K.R.; Methodology, B.A., M.N., N.N. and K.R.; Project administration, K.R. Resources, B.A., M.N., N.N. and K.R.; Software, B.A., M.N., N.N. and K.R.; Supervision, K.R.; Validation, B.A., M.N., N. N. and K.R; Visualization, B.A., M.N., N.N. and K.R.; Writing—original draft, B.A., M.N., N.N. and K.R; Data Visualization, Editing and Rewriting, B.A., M.N., N.N. and K.R.

Correspondence to Krishnaraj Ramaswamy.

The authors declare no competing interests.

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Open Access This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article's Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article's Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creativecommons.org/licenses/by/4.0/.

Reprints and Permissions

Baskaran, A., Manikandan, N., Nagaprasad, N. et al. Second law assessment of di methyl ether and its mixtures in domestic refrigeration system. Sci Rep 13, 275 (2023). https://doi.org/10.1038/s41598-023-27600-9

Download citation

Received: 24 September 2022

Accepted: 04 January 2023

Published: 06 January 2023

DOI: https://doi.org/10.1038/s41598-023-27600-9

Anyone you share the following link with will be able to read this content:

Sorry, a shareable link is not currently available for this article.

Provided by the Springer Nature SharedIt content-sharing initiative

By submitting a comment you agree to abide by our Terms and Community Guidelines. If you find something abusive or that does not comply with our terms or guidelines please flag it as inappropriate.